electrical voltage unbalance calculator
An unbalance of over 1 percent on voltage may be influential in the performance of the motor. It is a useful calculator for engineers, electricians, and technicians involved in power quality, energy audits, and industrial maintenance. It assists in maintaining efficient and dependable operation of equipment, as initiation of imbalance problems can be detected and eliminated prior to resulting in damage and unavailability. With this tool, you will be able to create a 3-phase system that will run to the safety standards and be as efficient as possible.
Suggested Reading
- online auto transformer calculator
- Motor Startup Current Conversion Calculator
- Battery Capacity Conversion Calculator
- Series Current Conversion Calculator
- Current Conversion Calculator
- Total Current Conversion Calculator
- earthing system calculator simple
- Terminal Voltage Conversion Calculator
- Generator Voltage Conversion Calculator
- Speed To Power Conversion Calculator
- No Load Voltage Conversion Calculator
- Flywheel Power Conversion Calculator
- Dbm To Current Conversion Calculator
- motor efficiency torque calculation helper
- Ac Current Conversion Calculator
- Va To Watts Conversion Calculator
- Volts To Watts Conversion Calculator
- arc flash safety distance calculator
Formula:
Steps:
01. Measure the three line-to-line voltages:
VRY, VYB, VRB
02. Calculate the average voltage:
03. Find the deviation for each phase:
04. Find the maximum deviation:
05. Apply the main formula:
name conversion chart

The measuring line voltages are 415, 411, and 410 volts.
The average voltage is (415 + 411 + 410 = 1236 / 3 = 412).
Voltage deviation for each phase is:
VD_ry = 415 − 412 = 3
VD_yb = 411 − 412 = |1|
VD_rb = 410 − 412 = |2|
Maximum deviation = 3
%Voltage Unbalance = (3 / 412) × 100 = 0.73%
The voltage unbalance is within the limit as per NEMA Standard.
Frequently Asked Questions - voltage unbalance Conversion FAQs:
How do I calculate voltage unbalance?
Voltage unbalance is given by the formula. Phase to Phase Variations in a 3-phase system are found by computing %Voltage Unbalance using the formula (Max Deviation from Average Voltage ÷ Average Voltage) x 100, where the deviation is taken from three phase line voltages (Vab, Vbc, Vca).
What is voltage error and how is it calculated?
At the time, voltage error was defined as the deviation between the actual and nominal voltages. This is computed as %Voltage Error = ((Measured Voltage – Nominal Voltage) ÷ Nominal Voltage) × 100 (Demetri & Butler, 1994), thus providing a means to test supply accuracy on distribution systems.
What is the acceptable limit for voltage unbalance?
IEEE Standard 141 and NEMA MG-1 recommend no more than 2 percent of voltage unbalance for three-phase motors. Beyond this may induce overheating, torque loss, and motor failure before its time.
Why does voltage unbalance occur in power systems?
Voltage unbalance can more often than not be traced back to imperfect load distribution, faulty transformers, single-phase load on three-phase lines, or problems in power factor correction devices, all leading to disintegration of system balance.
How does voltage unbalance affect equipment?
Voltage unbalance has the potential to cause excessive heat, lower efficiency, vibrations, and shorter lifespans of rotating equipment, making the detection and correction of suitable measures in electrical maintenance very important.