electrical voltage unbalance calculator
An unbalance of over 1 percent on voltage may be influential in the performance of the motor. It is a useful calculator for engineers, electricians, and technicians involved in power quality, energy audits, and industrial maintenance. It assists in maintaining efficient and dependable operation of equipment, as initiation of imbalance problems can be detected and eliminated prior to resulting in damage and unavailability. With this tool, you will be able to create a 3-phase system that will run to the safety standards and be as efficient as possible.
Suggested Reading
- arc flash safety distance calculator
- cable diameter calculator free
- PV system losses calculator online
- Charge To Current Conversion Calculator
- Transistor Base Current Conversion Calculator
- Micro Farad To Kvar Conversion Calculator
- Kva To Watts Conversion Calculator
- Earth Conductor Size Conversion Calculator
- Watts To Wh Conversion Calculator
- Current Imbalance Conversion Calculator
- motor efficiency torque calculation helper
- No Load Current Conversion Calculator
- Output Power Conversion Calculator
- Hv High Voltage Cable Sizing Conversion Calculator
- Amps To Kw Conversion Calculator
- cable amperage calculator simple
- Three Phase Power Conversion Calculator
- Single Phase Power Conversion Calculator
Formula:
Steps:
01. Measure the three line-to-line voltages:
VRY, VYB, VRB
02. Calculate the average voltage:
03. Find the deviation for each phase:
04. Find the maximum deviation:
05. Apply the main formula:
name conversion chart

The measuring line voltages are 415, 411, and 410 volts.
The average voltage is (415 + 411 + 410 = 1236 / 3 = 412).
Voltage deviation for each phase is:
VD_ry = 415 − 412 = 3
VD_yb = 411 − 412 = |1|
VD_rb = 410 − 412 = |2|
Maximum deviation = 3
%Voltage Unbalance = (3 / 412) × 100 = 0.73%
The voltage unbalance is within the limit as per NEMA Standard.
Frequently Asked Questions - voltage unbalance Conversion FAQs:
How do I calculate voltage unbalance?
Voltage unbalance is given by the formula. Phase to Phase Variations in a 3-phase system are found by computing %Voltage Unbalance using the formula (Max Deviation from Average Voltage ÷ Average Voltage) x 100, where the deviation is taken from three phase line voltages (Vab, Vbc, Vca).
What is voltage error and how is it calculated?
At the time, voltage error was defined as the deviation between the actual and nominal voltages. This is computed as %Voltage Error = ((Measured Voltage – Nominal Voltage) ÷ Nominal Voltage) × 100 (Demetri & Butler, 1994), thus providing a means to test supply accuracy on distribution systems.
What is the acceptable limit for voltage unbalance?
IEEE Standard 141 and NEMA MG-1 recommend no more than 2 percent of voltage unbalance for three-phase motors. Beyond this may induce overheating, torque loss, and motor failure before its time.
Why does voltage unbalance occur in power systems?
Voltage unbalance can more often than not be traced back to imperfect load distribution, faulty transformers, single-phase load on three-phase lines, or problems in power factor correction devices, all leading to disintegration of system balance.
How does voltage unbalance affect equipment?
Voltage unbalance has the potential to cause excessive heat, lower efficiency, vibrations, and shorter lifespans of rotating equipment, making the detection and correction of suitable measures in electrical maintenance very important.