Voltage Unbalance Calculator: 3 Phase System % Deviation Tool

    Created by Md jony islam

    voltage unbalance Conversion Calculator

    Volts can be readily estimated for unbalance in a 3-phase system, through line voltages. Calculate the % deviation on the NEMA standard in order to have a better electrical load balance. Calculation of voltage unbalance plays a crucial role in ensuring the efficiency and safety of the 3-phase electrical systems. It is a comparison of the deviation of the phase voltages from the average voltage, which is normally shown as a percentage. It is easy to get an overview of whether or not the system falls in an acceptable range (usually below 1 percent) simply by utilizing the standard formula: maximum deviation 100/average voltage. Any normal imbalance in voltages can result in excessive heating up, excess wastage of power, and in advance failure of motors and delicate equipment. The calculation is useful in locating unbalanced loads, wiring, or supply problems, so it is a critical measure of electrical diagnostics and maintenance.

    voltage unbalance percentage calculator

    Voltage Unbalance Calculator
    %

    Learn how we tools this below

    Add this tools to your site

    Buy me a for Source Code

    What do you need to know to calculate Voltage Unbalance?

    🙋 Try our Kva To Va Calculator . If you want to learn more about conversions using Electrical Engineering Project Calculators.

    electrical voltage unbalance calculator

    Formula:

    Voltage Unbalance (%) = (VMax deviationVaverage) × 100

    Steps:

    01. Measure the three line-to-line voltages:
    VRY, VYB, VRB

    02. Calculate the average voltage:

    Vavg = VRY + VYB + VRB3

    03. Find the deviation for each phase:

    ΔVRY = ∣VRY - VavgΔVYB = ∣VYB - VavgΔVRB = ∣VRB - Vavg

    04. Find the maximum deviation:

    Vmax deviation = max(ΔVRY, ΔVYB, ΔVRB,)

    05. Apply the main formula:

    Voltage Unbalance (%) = (VMax deviationVaverage) × 100

    name conversion chart

    Example Info
    Example

    The measuring line voltages are 415, 411, and 410 volts.

    The average voltage is (415 + 411 + 410 = 1236 / 3 = 412).

    Voltage deviation for each phase is:

    VD_ry = 415 − 412 = 3

    VD_yb = 411 − 412 = |1|

    VD_rb = 410 − 412 = |2|

    Maximum deviation = 3

    %Voltage Unbalance = (3 / 412) × 100 = 0.73%

    The voltage unbalance is within the limit as per NEMA Standard.

    Frequently Asked Questions - voltage unbalance Conversion FAQs:

    How do I calculate voltage unbalance?

    Voltage unbalance is given by the formula. Phase to Phase Variations in a 3-phase system are found by computing %Voltage Unbalance using the formula (Max Deviation from Average Voltage ÷ Average Voltage) x 100, where the deviation is taken from three phase line voltages (Vab, Vbc, Vca).

    What is voltage error and how is it calculated?

    At the time, voltage error was defined as the deviation between the actual and nominal voltages. This is computed as %Voltage Error = ((Measured Voltage – Nominal Voltage) ÷ Nominal Voltage) × 100 (Demetri & Butler, 1994), thus providing a means to test supply accuracy on distribution systems.

    What is the acceptable limit for voltage unbalance?

    IEEE Standard 141 and NEMA MG-1 recommend no more than 2 percent of voltage unbalance for three-phase motors. Beyond this may induce overheating, torque loss, and motor failure before its time.

    Why does voltage unbalance occur in power systems?

    Voltage unbalance can more often than not be traced back to imperfect load distribution, faulty transformers, single-phase load on three-phase lines, or problems in power factor correction devices, all leading to disintegration of system balance.

    How does voltage unbalance affect equipment?

    Voltage unbalance has the potential to cause excessive heat, lower efficiency, vibrations, and shorter lifespans of rotating equipment, making the detection and correction of suitable measures in electrical maintenance very important.

    About the Author

    Md Jony Islam

    Md Jony Islam: Multidisciplinary Engineer & Financial Expert:

    Md. Jony Islam is a highly skilled professional with expertise in electronics, electrical, mechanical, and civil engineering, as well as finance. Specializing in transformer service and maintenance for 33/11kV substations, he ensures reliable and efficient electrical systems. His mechanical engineering skills drive innovative designs, while his financial acumen supports effective project budgeting. With a strong foundation in civil engineering, he contributes to robust infrastructure development. Md. Jony Islam's multidisciplinary approach ensures efficiency, quality, and reliability across all projects.